Spoiler alert: Flexible ducting has just taken a massive hit. Under Approved Document F's 2026 edition (Volume 1: Residential), flexible ducting can only be used as a final connection to a fan spigot, and only up to 200mm long. Everywhere else in a dwelling's mechanical ventilation system, it's got to be rigid or semi-rigid ducting. Every contractor, developer, and FM team specifying ventilation should know what this update entails before it takes effect in 2027.
Approved Document F, Volume 1 (2026 edition) restricts flexible ductwork to a maximum of 200mm in length, used only for the final connection to a fan unit spigot on centralised continuous mechanical extract ventilation (MEV) or mechanical ventilation with heat recovery (MVHR) systems. That's just a short stub at the fan — not the standard length of duct that many contractors are still running through ceilings, or loft space.
Even within that 200mm allowance, the flexible section has to be installed with the full internal diameter maintained, with flow resistance kept to a minimum. No kinks, no compression, no slack.
The 2021 edition allowed flexible ductwork up to 1.5 metres, provided it was used only for final connections and met BSRIA's BG 43/2013 standard. The 2026 edition cuts that down to 200mm — a roughly 85% reduction in maximum permitted length.
The 2021 edition also just said rigid ducts "should be used wherever possible," without naming semi-rigid as a defined alternative. The 2026 edition is more precise: it explicitly names rigid or smooth semi-rigid ducting as the compliant choice for centralised MEV and MVHR systems — putting semi-rigid on equal footing with rigid metal duct for the first time.
There are several other changes from Part F 2021, and they apply across the whole system, not just the fan connection:
The 2026 edition doesn't spell out its reasoning line by line, but the direction of travel points at a few well-known problems with flexible duct in residential ventilation. Here's our speculation:
Elephant Duct doesn't suffer these problems. Our line of semi-rigid ducting is fire-rated up to Class B-s1, d0 and Class 1 (D.M. 26/06/84), carries an antimicrobial hygienic coating, and holds its shape without sagging, which we believe is precisely why the 2026 edition now names semi-rigid as a compliant alternative to rigid metal duct.
Yes, under paragraph 1.76 of the 2026 edition, "rigid or smooth semi-rigid ducts" are required for centralised continuous MEV and MVHR systems — these are the exact systems where flexible duct has just been cut to a maximum of 200mm. Semi-rigid ducting bends around joists, studwork, and tight loft runs the way rigid metal can't, while keeping the smooth bore and shape retention that flexible duct lacks.
Specifying or retrofitting a ventilation system that needs to meet Part F 2026? Talk to us about where semi-rigid ducting fits your project.
Approved Document F is periodically revised — always verify the current wording and effective dates against the live gov.uk publication before specifying or signing off installation work.